Estudo e projeto de controladores aplicados na malha de controle de corrente de um filtro ativo de potência paralelo

Detalhes bibliográficos
Ano de defesa: 2014
Autor(a) principal: Malvezzi, Victor Belieiro
Orientador(a): Não Informado pela instituição
Banca de defesa: Não Informado pela instituição
Tipo de documento: Dissertação
Tipo de acesso: Acesso aberto
Idioma: por
Instituição de defesa: Universidade Tecnológica Federal do Paraná
Cornelio Procopio
Programa de Pós-Graduação em Engenharia Elétrica
Programa de Pós-Graduação: Não Informado pela instituição
Departamento: Não Informado pela instituição
País: Não Informado pela instituição
Palavras-chave em Português:
Link de acesso: http://repositorio.utfpr.edu.br/jspui/handle/1/1200
Resumo: This work presents the study, design and implementation of three control strategies for compensating current in a single-phase Shunt Active Power Filter (SAPF), such as the conventional PI controller based on reference frame ( ), conventional PI controller based on reference frame ( ), PI plus resonant controller based on reference frame ( ) and PI plus resonant controller based on reference frame ( ). The DC bus voltage is controlled by using a linear PI controller. The SAPF consists of a full-bridge inverter connected to the grid. The main function of the shunt SAPF is to provide to the utility grid an adequate compensation current, containing the same amplitude and opposite phase of the load current harmonics. The algorithm used for obtaining the reference compensation current is based on the synchronous reference frame (SRF algorithm). Mathematical analyzes are developed in order to obtain the mathematical model which represents the SAPF physical system. In addition, it is presented a design methodology employed for obtaining the gains of the PI controllers used in both the compensation current and the DC-bus voltage loops. It is also presented methodology for tuning the resonant controllers. Simulation and experimental results are presented to validate the theoretical development and compare the performance of FAPP when submitted to the proposed control strategies.